ABB ACS580 — 3220 DC Link Undervoltage

Occurs when the DC-link voltage drops below the lower limit. Triggered by supply sag, phase loss or rectifier/capacitor issues.

Updated: 2026-07-05

Symptoms

  • 3220 on power-up or when load is applied
  • Frequent trips during supply fluctuations
  • Unexpected stop under load

Probable Causes

  • Supply voltage sag or brief interruption
  • Input phase loss
  • Weak/dried-out DC-link capacitors
  • Undersized supply / long cable run

Checkpoints

  • Measure supply voltage under load
  • Verify input phases and fuses
  • Read DC-link voltage from the panel
  • Assess supply transformer/cable capacity

Solution

If mains and connections are healthy, dried-out electrolytic capacitors cause the DC link to collapse under load; the board is repaired by recapping in the lab.