Siemens SINAMICS G120 — F30011 Line Phase Loss

Raised when loss of one input phase is detected. DC-link ripple increases and the rectifier is stressed.

Updated: 2026-07-05

Symptoms

  • F30011 under load
  • Increased DC-link ripple
  • Vibration/noise in the drive

Probable Causes

  • Blown input fuse
  • Loose/oxidized mains terminal
  • Mains phase imbalance
  • Contactor contact problem

Checkpoints

  • Measure all three input phases
  • Check fuses and terminals
  • Inspect contactor contacts
  • Assess mains balance

Solution

If mains is healthy, inspect the input rectifier stage or DC-link capacitors.