Yaskawa A1000 — oC Overcurrent

Occurs when output current exceeds the hardware limit. Motor/cable short, short ramp or output-stage failure trigger it.

Updated: 2026-07-05

Symptoms

  • oC at start/acceleration
  • Immediate fault with motor connected
  • May clear when tested without motor

Probable Causes

  • Motor cable short / ground fault
  • Too-short accel time (C1-01)
  • Output stage (IGBT) failure

Checkpoints

  • Megger the motor and cable
  • Increase accel time (C1-01)
  • Run without motor to assess the output stage

Solution

If the no-motor test still shows oC, the power board (IGBT + gate driver) is tested in the lab.